ESE,lightning arrester,early streamer emission,lighting conductor
Product Details:
| Place of Origin | Guangdong, China (Mainland) |
|---|---|
| Model Number | ESE68 |
Payment & Shipping Terms:
| Minimum Order Quantity: | 6 Piece/Pieces |
|---|---|
| Packaging Details: | 37 X 37 X 47 cm box |
| Delivery Time: | Within 11 days upon receipt of T/T |
| Payment Terms: | L/C,T/T |
| Supply Ability: | 100 Piece/Pieces per Month |
Detailed Product Description
Introduction of smart-ESE
1.Technical parameter:
Model number | REP-ESE68 |
Max. discharge current | ≥200KA |
Capacity against wind speed | ≥40m/s |
Length | 37cm |
Discharge time in advantage | 30 μs |
Protection radius | by caculate formula or table1 to table 3 |
Material | Stainless steel |
Standard | France NFC17-102 1995 |
2.discharge rod(lightning conductor) introduction and application
. a pick-up point of solid electric copper ,or stainless steel ,permanently connected to earth ,for discharge of collected lightning via a down conductor to earth.
.The upper electrodessparks emission
. a waterproof stainless boxconnected to earth
. trigger circuitinner box.
. The lower electrodesenergy collection
. principle of operation for this Smart-ESE surge protection collects energy form the atmospheric electrical field ,which builds up considerably in storm conditions, when lightning can occur. When the potential electrical field gradient increase , this energy ,accumulated in the electric device ,is discharged by sparking around the point this specific artificial ionization ,associated to the point effect phenomenon ,improves the attraction power of the lightning rod , and significantly increases the radius of protection.(surge protector) .
.advantageself-contained working, guaranteed wider range of protection, simple system, with less expensive installation costs ,electronic charge control and distribution in storm conditions, high reliability, maintenance free .
.protection radii:
when h∠5m:see table1~table3
when h≥5m:
Rp=√h(2D-h)+L(2D+L)
Rp: protection radius
h: actual height of lightning rod above the surface area to be protected
D:20/40/60m : depending on the protection level required
L=V*T(V=1m/us T: Discharge time in advance)
3.PROTECTION RADIUS
TABLE 1
High protectionD=20m | ||||||||||
h | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 10 | 15 | Maxi(20) |
ESE68 | 19 | 28 | 38 | 47 | 48 | 48 | 48 | 48 | 49 | 50 |
TABLE 2
Medium protection D=45m | ||||||||||
h | 2 | 3 | 4 | 5 | 6 | 8 | 10 | 15 | 20 | Maxi(45) |
ESE68 | 26 | 38 | 50 | 63 | 64 | 65 | 66 | 68 | 70 | 75 |
TABLE 3
Standard protection D=60m | ||||||||||
h | 2 | 3 | 4 | 5 | 6 | 8 | 10 | 20 | 45 | Maxi(60) |
ESE68 | 28 | 42 | 56 | 71 | 72 | 73 | 74 | 80 | 88 | 90 |
h=actual height of lightning rod above the surface area to be protectedm.
Key words: ese,early streamer emission,lightning conductor,air terminal,lightning rod,lightning protection,lightning arrester,lightning protector,discharge rod,thunder protection,
ESE,lightning arrester,early streamer emission,lighting conductor
Other Products from this Supplier
See more
lightning rod, lightning conductor, early streamer emission products from this supplier.
Products
- Lightning rod [8]
- Power Surge Protective Device [14]
- Signal Surge Protective Device [32]
- grouding [3]
Company Info
Guangzhou Panyu Rison Lightning Protection Technology Co., Ltd.
[China (Mainland)]
[Verified Member]
City: Guangzhou
Province/State: Guangdong
Country/Region : China (Mainland)
Business Type:Manufacturer
Online Postings: Products