Guangzhou Panyu Rison Lightning Protection Technology Co., Ltd.

home products Lightning rod ESE,air terminal,lightning rod,discharge rod,lightning arrester

ESE,air terminal,lightning rod,discharge rod,lightning arrester

Product Details:

Place of Origin Guangdong, China (Mainland)
Model Number ESE18

Payment & Shipping Terms:

Minimum Order Quantity: 6 Piece/Pieces
Packaging Details: 37 X 37 X 47cm box
Delivery Time: Within 12 days upon receipt of T/T
Payment Terms: L/C,T/T
Supply Ability: 100 Piece/Pieces per Month

Detailed Product Description


1.       Technical parameter:

 

Model number

REP-ESE18

Max. discharge current

≥200KA

Capacity against wind speed

≥40m/s

Length

39cm

Discharge time in advantage

20 μs

Protection radius

by caculate formula or table1 to table 3

Material

Stainless steel

Standard

France NFC17-102  (1995)

 

2.discharge rod(lightning conductor) introduction and application

 

. A pick-up point of solid electric copper ,or stainless steel ,permanently connected to earth ,for discharge of collected lightning via a down conductor to earth.

 

.The upper electrodessparks emission

. A waterproof stainless boxconnected to earth

. trigger circuitinner box.

. The lower electrodesenergy collection

 

. Principle of operation for this Smart-ESE surge protection collects energy form the atmospheric electrical field ,which builds up considerably in storm conditions, when lightning can occur. When the potential electrical field gradient increase , this energy ,accumulated in the electric device ,is discharged by sparking around the point  this specific artificial ionization ,associated to the point effect phenomenon ,improves the attraction power of the lightning rod , and significantly increases the radius of protection.(surge protector) .

.advantageself-contained working, guaranteed wider range of protection, simple system, with less expensive installation costs ,electronic charge control and distribution in storm conditions, high reliability, maintenance free .

 

Protection radii:

when h∠5m:see table1~table3

when h≥5m:

Rp=√h(2D-h)+L(2D+L)

Rp: protection radius

h: actual height of lightning rod above the surface area to be protected

D:20/40/60m : depending on the protection level required

L=V*T(V=1m/us   T: Discharge time in advance)

 

3.PROTECTION RADIUS

 

TABLE 1

High protectionD=20m

h

2

3

4

5

6

7

8

10

15

Maxi(20)

ESE18

15

22

30

37

37

37

38

38

49

50

 

TABLE 2

Medium protection D=45m

h

2

3

4

5

6

8

10

15

20

Maxi(45)

ESE18

20

31

41

51

52

53

54

57

60

65

 

TABLE 3

Standard protection D=60m

h

2

3

4

5

6

8

10

20

45

Maxi(60)

ESE18

22

35

46

58

59

60

62

69

78

80

 

h=actual height of lightning rod above the surface area to be protectedm.

 

Key words:  ese,early streamer emission,lightning conductor,air terminal,lightning rod,lightning protection,lightning arrester,lightning protector,discharge rod,thunder protection,

ESE,air terminal,lightning rod,discharge rod,lightning arrester ESE,air terminal,lightning rod,discharge rod,lightning arrester

Send your message to this supplier
« Prev Product 1 2 3 4 5 6 7 ... Next Product »

Other Products from this Supplier

Company Info

Guangzhou Panyu Rison Lightning Protection Technology Co., Ltd.
[China (Mainland)]
[Verified Member]

City: Guangzhou
Province/State: Guangdong
Country/Region : China (Mainland)

Business Type:Manufacturer

View Contact Details

Email this page Bookmark this page Print this Page